The Code may include references to such other rules of special types, such as those of the Medical Care Commission and the Department of Public Instruction as may be useful to persons using the Code. No rule issued by any agency other than the Building Code Council or Residential Code Council shall be construed as a part of the Code, nor supersede that Code, it being intended that they be presented with the Code for information only.
For purposes of this subsection, "migrant housing" and "migrant" shall be defined as in G.S. 95-223.
A local government may not adopt any ordinance in conflict with the exemption provided by subsection (c1) of this section. No local ordinance or regulation shall be construed to limit the exemption provided by subsection (c1) of this section.
OFFICIAL OR AGENCY | NUMBER OF COPIES |
State Departments and Officials | |
Governor.............................................................................................................. | 1 |
Lieutenant Governor........................................................................................... | 1 |
Auditor................................................................................................................ | 1 |
Treasurer.............................................................................................................. | 1 |
Secretary of State................................................................................................ | 1 |
Superintendent of Public Instruction.................................................................. | 1 |
Attorney General (Library).................................................................................. | 1 |
Commissioner of Agriculture.............................................................................. | 1 |
Commissioner of Labor....................................................................................... | 1 |
Commissioner of Insurance................................................................................. | 1 |
Department of Environmental Quality................................................................ | 1 |
Department of Health and Human Services........................................................ | 1 |
Division of Prisons of the Department ofAdult Correction | 1 |
Division of Juvenile Justice of the Department of Public Safety.... | 1 |
Board of Transportation...................................................................................... | 1 |
Utilities Commission........................................................................................... | 1 |
Department of Administration............................................................................ | 1 |
Clerk of the Supreme Court................................................................................ | 1 |
Clerk of the Court of Appeals............................................................................. | 1 |
Department of Natural and Cultural Resources [State Library].......................... | 1 |
Supreme Court Library........................................................................................ | 1 |
Legislative Library............................................................................................... | 1 |
Office of Administrative Hearings...................................................................... | 1 |
Rules Review Commission.................................................................................. | 1 |
Schools | |
All state-supported colleges and universities | |
in the State of North Carolina...................................................................... | * 1 each |
Local Officials | |
Clerks of the Superior Courts.............................................................................. | 1 each |
Chief Building Inspector of each incorporated | |
municipality or county................................................................................. | 1 |
In addition, the Building Code Council shall make additional copies available at such price as it shall deem reasonable to members of the general public. The proceeds from sales of the Building Code shall be credited to the Insurance Regulatory Fund under G.S. 58-6-25.
SECTION 1008-SPECIAL SAFETY TO LIFEREQUIREMENTS APPLICABLE TO EXISTING HIGH-RISE BUILDINGS
1008 - GENERAL.
NOTE: Suggested reasonable time and procedures for owners to respond to the building official's request is as follows:
NOTE: Suggested Time Period For Compliance:
SUGGESTED TIME PERIOD FOR COMPLIANCE | ||||
CLASS I | CLASS II | CLASS III | TIME FOR | |
ITEM | (SECTION) | (SECTION) | (SECTION) | COMPLETION |
Signs in Elevator Lobbiesand Elevator Cabs | 1008.2(h) | 1008.3(h) | 1008.4(h) | 180 days |
Emergency Evacuation Plan | 1008(b) | NOTE: | 180 days | |
Corridor Smoke Detectors | ||||
(Includes alternative | ||||
door closers) | 1008.2(c) | 1008.3(c) | 1008.4(c) | 1 year |
Manual Fire Alarm | 1008.2(a) | 1008.3(a) | 1008.4(a) | 1 year |
Voice Communication | ||||
System Required | 1008.2(b) | 1008.3(b) | 1008.4(b) | 2 years |
Smoke Detectors Required | 1008.2(c) | 1008.3(c) | 1008.4(c) | 1 year |
Protection and Fire Stopping | ||||
for Vertical Shafts | 1008.2(f) | 1008.3(f) | 1008.4(f) | 3 years |
Special Exit Requirements- | ||||
Number, Location and | ||||
Illumination to be in | ||||
accordance with | ||||
Section 1007 | 1008.2(e) | 1008.3(e) | 1008.4(e) | 3 years |
Emergency Electrical | ||||
Power Supply | 1008.2(d) | 1008.3(d) | 1008.4(d) | 4 years |
Special Exit Facilities | ||||
Required | 1008.2(e) | 1008.3(e) | 1008.4(e) | 5 years |
Compartmentation for | ||||
Institutional Buildings | 1008.2(f) | 1008.3(f) | 1008.4(f) | 5 years |
Emergency Elevator | ||||
Requirements | 1008.2(h) | 1008.3(h) | 1008.4(h) | 5 years |
Central Alarm Facility | ||||
Required | 1008.(i)3 | 1008.4(i) | 5 years | |
Areas of Refuge Required | ||||
on Every Eighth Floor | 1008.4(j) | 5 years | ||
Smoke Venting | 1008.4(k) | 5 years | ||
Fire Protection of | ||||
Electrical Conductors | 1008.4(l) | 5 years | ||
Sprinkler System Required | 1008.4(m) | 5 years |
FOOTNOTE: Emergency Plan. - Owners, operators, tenants, administrators or managers of high-rise buildings should consult with the fire authority having jurisdiction and establish procedures which shall include but not necessarily be limited to the following:
1008.1 - ALL EXISTING BUILDINGS SHALL BE CLASSIFIED AS CLASS I, II AND III ACCORDING TO TABLE 1008.1.
TABLE 1008.1
Scope
CLASS (1) | OCCUPANCY GROUP (3)(4) | OCCUPIED FLOOR ABOVE AVERAGE GRADE EXCEEDING HEIGHT (2) |
CLASS I | Group R-Residential | 60' but less than 120' above average grade or 6 but less than 12 stories above |
Group B-Business | ||
Group E-Educational | ||
Group A-Assembly | ||
Group H-Hazardous | ||
Group I-Institutional-Restrained | ||
Group I-Institutional-Unrestrained | 36' but less than 60' above average grade or 3 but less than 6 stories above average grade. | |
CLASS II | Group R-Residential | 120' but less than 250' above average grade or 12 but less than 25 stories above average grade. |
Group B-Business | ||
Group E-Educational | ||
Group A-Assembly | ||
Group H-Hazardous | ||
Group I-Institutional-Restrained | ||
Group I-Institutional-Unrestrained | 60' but less than 250' above average grade or 6 but less than 25 stories above average grade. | |
CLASS III | Group R-Residential | 250' or 25 stories above average grade. |
Group B-Business | ||
Group E-Educational Group I-Institutional Group A-Assembly Group H-Hazardous |
NOTE 1: The entire building shall comply with this section when the building has an occupied floor above the height specified, except that portions of the buildings which do not exceed the height specified are exempt from this section, subject to the following provisions:
NOTE 2: The height described in Table 1008.1 shall be measured between the average grade outside the building and the finished floor of the top occupied story.
NOTE 3: Public parking decks meeting the requirements of Section 412.7 and less than 75 feet in height are exempt from the requirements of this section when there is no other occupancy above or below such deck.
NOTE 4: Special purpose equipment buildings, such as telephone equipment buildings housing the equipment only, with personnel occupant load limited to persons required to maintain the equipment may be exempt from any or all of these requirements at the discretion of the Engineering and Building Codes Division provided such special purpose equipment building is separated from other portions of the building by two-hour fire rated construction.
1008.2-REQUIREMENTS FOR EXISTING CLASS I BUILDINGS.
All Class I buildings shall be provided with the following:
NOTE 1: Limited area sprinklers may be supplied from the domestic water system provided the domestic water system is designed to support the design flow of the largest number of sprinklers in any one of the enclosed areas. When supplied by the domestic water system, the maximum number of sprinklers in any one enclosed room or area shall not exceed 20 sprinklers which must totally protect the room or area.
OFFICIAL OR AGENCY | NUMBER OF COPIES |
State Departments and Officials | |
Governor.............................................................................................................. | 1 |
Lieutenant Governor........................................................................................... | 1 |
Auditor................................................................................................................ | 1 |
Treasurer.............................................................................................................. | 1 |
Secretary of State................................................................................................ | 1 |
Superintendent of Public Instruction................................................................... | 1 |
Attorney General (Library).................................................................................. | 1 |
Commissioner of Agriculture.............................................................................. | 1 |
Commissioner of Labor....................................................................................... | 1 |
State Fire Marshal................................................................................ | 1 |
Department of Environmental | |
Quality........................................................................................................ | 1 |
Department of Health and Human Service.......................................................... | 1 |
Division of Adult Correction and Juvenile Justice of the | |
Department of Public Safety...................................................................... | 1 |
Board of Transportation....................................................................................... | 1 |
Utilities Commission........................................................................................... | 1 |
Department of Administration............................................................................ | 1 |
Clerk of the Supreme Court................................................................................ | 1 |
Clerk of the Court of Appeals............................................................................. | 1 |
Department of Natural and Cultural Resources [State | |
Library]....................................................................................................... | 1 |
Supreme Court Library........................................................................................ | 1 |
Legislative Library.............................................................................................. | 1 |
Office of Administrative Hearings...................................................................... | 1 |
Rules Review Commission.................................................................................. | 1 |
Schools | |
All state-supported colleges and universities | |
in the State of North Carolina................................................................... | *1 each |
Local Officials | |
Clerks of the Superior Courts.............................................................................. | 1 each |
Chief Building Inspector of each incorporated | |
municipality or county............................................................................... | 1 |
In addition, the Building Code Council and Residential Code Council shall make additional copies available at such price as it shall deem reasonable to members of the general public. The proceeds from sales of the Code, or any part of the Code, shall be credited to the Insurance Regulatory Fund under G.S. 58-6-25.
1008.3 - REQUIREMENTS FOR EXISTING CLASS II BUILDINGS.
All Class II buildings must meet the following requirements:
NOTE 1: This system shall function so that in the event of one circuit or speaker being damaged or out of service, the remainder of the system shall continue to be operable.
NOTE 2: This system shall include provisions for silencing the fire alarm devices when the loud speakers are in use, but only after the fire alarm devices have operated initially for not less than 15 seconds.
EXCEPTION: Shaft wall openings protected in accordance with NFPA No. 90A and openings connected to metal ducts equipped with approved fire dampers within the shaft wall opening do not need any additional protection.
NOTE: Manually operated cars are considered to be in compliance with this provision if each car is equipped with an audible or visual alarm to signal the operator to return to the designated level.
NOTE: Detectors in HVAC systems used for fan shut down need not be annunciated.
1008.4 - REQUIREMENTS FOR EXISTING CLASS III BUILDINGS.
All Class III Buildings shall be provided with the following:
NOTE 1: This system shall be designed so that in the event of one circuit or speaker being damaged or out of service the remainder of the system shall continue to be operable.
NOTE 2: This system shall include provisions for silencing the fire alarm devices when the loud speakers are in use, but only after the fire alarm devices have operated initially for not less than 15 seconds.
NOTE: The one-way and two-way voice communication systems may be combined.
NOTE: This elevator will have a manual control in the cab which will override all other controls including floor call buttons and door controls.
NOTE: Manually operated cars are considered to be in compliance with this provision if each car is equipped with an audible or visual alarm to signal the operator to return to the designated level.
NOTE: Emergency power supply can be sized for nonsimultaneous use of the primary and secondary emergency elevators.
NOTE: Detectors in HVAC systems used for fan shut down need not be annunciated.
NOTE: Not required in buildings where there is a status indicator at the main elevator lobby.
The sprinkler system must be equipped with a water flow and supervisory signal system that will transmit automatically a water flow signal directly to the fire department or to an independent signal monitoring service satisfactory to the fire department.
N.C. Gen. Stat. § 143-138