Exceptions:
"Water-reactive material."
"Class 3."
"Class 2."
"Class 1."
Exception: Water-reactive solids and liquids stored in tanks.
Class 2 water-reactive solids and liquids shall not be stored in basements unless such materials are stored in closed water-tight containers or tanks.
Class 3 water-reactive solids and liquids shall not be stored in basements.
Class 2 or 3 water-reactive solids and liquids shall not be stored with flammable liquids.
Class 2 water-reactive solids and liquids shall be limited to piles not greater than 1,000 cubic feet (28 m3).
Aisle widths between piles shall not be less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.
Replaces: 1301:7-7-44.
Ohio Admin. Code 1301:7-7-67
Five Year Review (FYR) Dates: 12/15/2022
Promulgated Under: 119.03
Statutory Authority: 3737.22, 3737.82, 3737.83
Rule Amplifies: 3737.82, 3737.83, 3737.22
Prior Effective Dates: 07/01/1979, 06/01/1985, 06/15/1992, 07/01/1993, 09/01/1995, 03/30/1998, 09/01/2005, 07/01/2007, 11/01/2011