Exceptions:
Oxidizing cryogenic fluids, including oxygen, shall comply with rule 1301:7-7-63 of the Administrative Code, as applicable.
Flammable cryogenic fluids, including hydrogen, methane and carbon monoxide, shall comply with rules 1301:7-7-23 and 1301:7-7-58 of the Administrative Code, as applicable.
Inert cryogenic fluids, including argon, helium and nitrogen, shall comply with ANSI/CGA P-18 as listed in rule 1301:7-7-80 of the Administrative Code.
"Cryogenic container."
"Cryogenic fluid."
"Cryogenic vessel."
"Flammable cryogenic fluid."
"Low-pressure tank."
Exception: DOTn-specified containers with an internal volume of 2 cubic feet ( 0.057 m3) or less.
Exceptions:
Where a schematic drawing is provided, it shall be attached to the container and maintained in a legible condition.
Table 5504.3.1.1 Separation of stationary containers from exposure hazards
Exposure | Minimum distance (feet) |
Buildings, regardless of construction type | 1 |
Building exits | 10 |
Wall openings | 1 |
Air intakes | 10 |
Lot lines | 5 |
Places of public assembly | 50 |
Nonambulatory patient areas | 50 |
Combustible materials such as paper, leaves, weeds, dry grass or debris | 15 |
Other hazardous materials | In accordance with rule 1301:7-7-50 of the Administrative Code |
Exception: These provisions shall not apply where it is determined by the fire code official that the container does not constitute a hazard, after consideration of special features such as crushed rock utilized as a heat sink, topographical conditions, nature of occupancy, proximity to structures on the same or adjacent property, and the capacity and construction of containers and character of fluids to be stored.
Table 5504.3.1.2.1 Separation of portable containers from exposure hazards
Exposure | Minimum distance (feet) |
Building exits | 10 |
Wall openings | 1 |
Air intakes | 10 |
Lot lines | 5 |
Combustible materials such as paper, leaves, weeds, dry grass or debris | 15 |
Other hazardous materials | In accordance with rule 1301:7-7-50 of the Administrative Code |
For SI: 1 foot = 304.8
Exception: These provisions shall not apply where it is determined by the fire code official that the container does not constitute a hazard.
Exception: Cryogenic fluids that can be demonstrated not to create harmful vapors.
Carts and trucks used to transport cryogenic containers shall be designed to provide a stable base for the commodities to be transported and shall have a means of restraining containers to prevent accidental dislodgment.