"Dry cleaning."
"Dry cleaning plant."
"Dry cleaning room."
"Dry cleaning system."
"Solvent or liquid classifications."
"Class I solvents."
Class II solvents.
"Class IIIA solvents."
"Class IIIB solvents."
"Class IV solvents."
Spotting and pretreating operations conducted in accordance with paragraph (F)(2106) of this rule shall not change the type of the dry cleaning plant.
Exception: Dry cleaning units are not required to be provided with exhaust ventilation where an exhaust hood is installed immediately outside of and above the loading door which operates at an airflow rate as follows:
Q = 100 x ALD (Equation 21-1)
where:
Q = flow rate exhausted through the hood, cubic feet per minute (m3/s).
ALD = area of the loading door, square feet (m2).
Exception: Solvent storage tanks installed underground, in vaults or in special enclosures in accordance with rule 1301:7-7-57 of the Administrative Code.
Exception: As provided in NFPA 32 as listed in rule 1301:7-7-80 of the Administrative Code for inside storage or treatment tanks.
Exceptions:
Exception: Where approved, a manual steam jet not less than 3/4 inch (19 mm) with a continuously available steam supply at a pressure not less than 15 pounds per square inch gauge (psig) (103 kPa) is allowed to be substituted for the automatic fire-extinguishing system.
Replaces: 1301:7-7-12.
Ohio Admin. Code 1301:7-7-21
Five Year Review (FYR) Dates: 12/15/2022
Promulgated Under: 119.03
Statutory Authority: 3737.83, 3737.82, 3737.22
Rule Amplifies: 3737.22, 3737.83, 3737.82
Prior Effective Dates: 07/01/1979, 06/01/1985, 06/15/1992, 07/01/1993, 09/01/1995, 03/30/1998, 09/01/2005, 07/01/2007, 11/01/2011