"Flame spread."
"Flame spread index."
"Interior floor-wall base."
"Site-fabricated stretch system."
"Smoke-developed index."
"Filling material." Means cotton, wool, kapok, feathers, down, hair, liquid, or any other natural or manmade material or substance that is used or can be used for stuffing in seating furniture.
"Public occupancy." Means all of the following:
"Seating furniture." Includes the cushions or pillows belonging to or forming a part of the furniture, the structural unit, and the filling material and its container or covering, and any article of furniture, including children's furniture that can be used as a support for an individual, or their limbs or feet, when sitting or resting in an upright or reclining position and that either:
Seating furniture does not include, except if intended for use by children or in facilities designed for the care or treatment of humans, any of the following:
"Sell." Includes sell, offer, or expose for sale, barter, trade, deliver, give away, rent, consign, lease, possess for sale, or dispose of in any other commercial manner.
Exceptions:
Table 803.3 Interior wall and ceiling finish requirements by occupancyk
Group | Sprinklered1 | Nonsprinklered | ||||
Interior exit stairways and ramps and exit passageways a b | Corridors and enclosure for exit access stairwaysand exit access ramps | Rooms and enclosed spacesc | Interior exit stairways and ramps and exit passagewaysa,b | Corridors and enclosure for stairways and exit access ramps | Rooms and enclosed spacesc | |
A-1 & A-2 | B | B | C | A | Ad | Be |
A-3f, A-4, A-5 | B | B | C | A | Ad | C |
B, E, M, R-1, R-4 | B | C | C | A | B | C |
F | C | C | C | B | C | C |
H | B | B | Cg | A | A | B |
I-1 | B | C | C | A | B | B |
I-2 | B | B | Bh,i | A | A | B |
I-3 | A | Ai | C | A | A | B |
I-4 | B | B | Bh,i | A | A | B |
R-2 | C | C | C | B | B | C |
R-3 | C | C | C | C | C | C |
S | C | C | C | B | B | C |
U | No restrictions | No restrictions |
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m2.
Exception: When the interior trim material has been tested as an interior finish in accordance with NFPA 286 as listed in rule 1301:7-7-80 of the Administrative Code and complies with the acceptance criteria in paragraph (C)(1)(b)(i)(803.1.2.1) of this rule, it shall not be required to be tested for flame spread index in accordance with ASTM E 84 or UL 723 as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Floor finishes and coverings of a traditional type, such as wood, vinyl, linoleum or terrazzo, and resilient floor covering materials that are not composed of fibers.
Exception: Where a building is equipped throughout with an automatic sprinkler system in accordance with paragraph (C)(3)(a) (i)(903.3.1.1) or (C)(3)(a)(ii)(903.3.1.2) of rule 1301:7-7-09 of the Administrative Code, Class II materials shall be permitted in any area where Class I materials are required and materials complying with DOC FF-1 "pill test" (CPSC 16 CFR Part 1630 as listed in rule 1301:7-7-80 of the Administrative Code or with ASTM D 2859 as listed in rule 1301:7-7-80 of the Administrative Code shall be permitted in any area where Class II material are required.
Exception: Interior trim materials that comply with paragraph (D)(1)( 804.1) of this rule.
Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Upholstered furniture belonging to the patients in sleeping rooms of nursing homes (Group I-2), provided that a smoke detector is installed in such rooms. Battery-powered, single-station smoke alarms shall be allowed.
Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
Exception: Upholstered furniture in rooms and spaces protected by an approved automatic sprinkler system installed in accordance with paragraph (C)(3)(a)(i) (903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
"NOTICE THIS ARTICLE IS MANUFACTURED FOR USE IN PUBLIC OCCUPANCIES AND MEETS THE FLAMMABILITY REQUIREMENTS OF CALIFORNIA BUREAU OF HOME FURNISHINGS AND THERMAL INSULATION TECHNICAL BULLETIN 133. HOWEVER, CARE SHOULD BE EXERCISED NEAR OPEN FLAME AND WITH BURNING CIGARETTES."
Exceptions:
Fixed or movable walls and partitions, paneling, wall pads and crash pads, applied structurally or for decoration, acoustical correction, surface insulation or other purposes, shall be considered interior finish, shall comply with paragraph (C)(803) of this rule and shall not be considered decorative materials or furnishings.
Exceptions:
Exceptions:
Exceptions:
Exceptions:
Exception: Where the aggregate area of foam plastic signs is less than 10 per cent of the floor area or wall area of the room or space in which the signs are located, whichever is less, subject to the approval of the fire code official.
Exception: Lockers constructed entirely of wood and noncombustible materials shall be permitted to be used wherever interior finish materials are required to meet a Class C classification in accordance with paragraph (C)(1)(a)(803.1.1) of this rule.
Replaces: 1301:7-7-08.
Ohio Admin. Code 1301:7-7-08
Five Year Review (FYR) Dates: 12/15/2022
Promulgated Under: 119.03
Statutory Authority: 3737.22, 3737.82, 3737.83
Rule Amplifies: 3737.22, 3737.82, 3737.83, 3737.842
Prior Effective Dates: 07/01/1979, 06/01/1985, 06/15/1992, 07/01/1993, 09/01/1995, 03/30/1998, 11/20/1998, 09/01/2005, 07/01/2007, 11/01/2011