Section 255.375 - Service lines: plastic
(a) Each plastic service outside a building must be installed below ground level, except that:
(1) it may be installed in accordance with section 255.321(l) of this Part; and
(2) it may terminate above ground level and outside the building if:
(i) the aboveground part of the plastic service line is protected against deterioration and external damage.
(ii) the plastic service line is not used to support external loads.
(b) Each plastic service line inside a building must be protected against external damage and must not be exposed.