N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 4-12.7

Current through Register Vol. 46, No. 45, November 2, 2024
Section 4-12.7 - Automatic-maximum firing rate over 20 gallons per hour

The burner shall be equipped with a proved pilot and the pilot trial-for-ignition period shall not exceed 15 seconds. The burner shall be so designed and installed that the main oil valve shall open only after the pilot is proven and either such pilot shall automatically shut off within 60 seconds after the main oil valve opens or the pilot sensing device shall be automatically de-energized. The main flame trial-for-ignition period shall not exceed 60 seconds and the main flame shall be continually supervised while the burner is firing. The electrical circuit to the main fuel valve shall be automatically de-energized within four seconds after flame failure and the de-energized valve shall close automatically within the next five seconds.

N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 4-12.7