On all manual or automatic oil-fired boilers having a firing rate of three gallons per hour or less, the main flame trial-for-ignition period shall not exceed 90 seconds. Upon flame failure, the main oil valve shall close automatically within 90 seconds.
N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 4-12.3