UPC section 609.1 is amended to read as follows:
UPC section 609.6 is amended to read as follows:
UPC section 609.10 is amended to read as follows:
UPC section 609.11 is amended to read as follows:
Water meters shall be located in an approved location inside a building as close as possible to the point of entrance of the potable water supply pipe, installed at least 12 inches above the finished floor, and readily accessible. All water meter installations shall be rigidly supported with a permanent support in order to prevent the meter from vibrating when the water is passing through it.
Exceptions:
Where installation inside a building is not possible, the water meter may be installed in an enclosed structure not subject to flooding, high groundwater, or surface drainage runoff, provided the meter is protected from freezing. Provisions shall be made to install the meters above grade when possible. When installed below grade, the top of the structure shall be located at least 12 inches above the finished grade, be secured, and be accessible. This structure shall not be connected to any storm or sanitary sewer system.
Minn. R. agency 222, ch. 4714, pt. 4714.0609