Minn. R. agency 222, ch. 4714, pt. 4714.0313

Current through Register Vol. 49, No. 20, November 12, 2024
Part 4714.0313 - HANGERS AND SUPPORTS

UPC section 313.7 is deleted in its entirety.

Subpart 1.Section 313.

Table 313.3 is amended to read as follows:

TABLE 313.3
HANGERS AND SUPPORTS
MATERIALSTYPES OF JOINTSHORIZONTALVERTICAL
Cast Lead and Oakum 5 feet, except 10 feet where 10 foot lengths are installed1,2,3 Base and each floor, not to exceed 15 feet
Compression Gasket Every other joint, unless over 4 feet then support each joint1,2,3 Base and each floor, not to exceed 15 feet
Cast-iron Hubless Shielded Coupling Every other joint, unless over 4 feet then support each joint1,2,3,4 Base and each floor, not to exceed 15 feet
Copper & Copper Alloys Soldered, Brazed, Threaded, or Mechanical 1-1/2 inches and smaller, 6 feet; 2 inches and larger, 10 feet Each floor, not to exceed 10 feet5
Steel Pipe for Water or DWV Threaded or Welded 3/4 inch and smaller, 10 feet; 1 inch and larger, 12 feet Every other floor, not to exceed 25 feet5
Steel Pipe for Gas Threaded or Welded 1/2 inch, 6 feet; 3/4 inch and 1 inch, 8 feet; 1-1/4 inches and larger, 10 feet 1/2 inch, 6 feet; 3/4 inch and 1 inch, 8 feet; 1-1/4 inches every floor level
Schedule 40 PVC and ABSDWV Solvent Cemented All sizes, 4 feet; allow for expansion every 30 feet3,6 Base and each floor; provide mid-story guides; provide for expansion every 30 feet6
CPVC Solvent Cemented 1 inch and smaller, 3 feet; 1-1/4 inches and larger, 4 feet Base and each floor; provide mid-story guides
CPVC-AL-CPVC Solvent Cemented 1/2 inch, 5 feet; 3/4 inch, 65 inches; 1 inch, 6 feet Base and each floor; provide mid-story guides
Lead Wiped or Burned Continuous Support Not to exceed 4 feet
Steel Mechanical In accordance with standards acceptable to the Authority Having Jurisdiction
PEX Cold Expansion, Insert, and Compression 1 inch and smaller, 32 inches; 1-1/4 inches and larger, 4 feet Base and each floor; provide mid-story guides
PEX-AL-PEX Metal Insert and Metal Compression 1/2 inch; 3/4 inch; 1 inch All sizes 98 inches Base and each floor; provide mid-story guides
PE-AL-PE Metal Insert and Metal Compression 1/2 inch; 3/4 inch; 1 inch All sizes 98 inches Base and each floor; provide mid-story guides
PE-RT Insert and Compression 1 inch and smaller, 32 inches; 1-1/4 inches and larger, 4 feet Base and each floor; provide mid-story guides
Polypropylene (PP) Fusion Weld (socket, butt, saddle, electrofusion), Threaded (metal threads only), or Mechanical 1 inch and smaller, 32 inches; 1-1/4 inches and larger, 4 feet Base and each floor; provide mid-story guides

For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm

Notes:

1 Support adjacent to joint, not to exceed 18 inches (457 mm).

2 Brace not to exceed 40-foot (12,192 mm) intervals to prevent horizontal movement.

3 Support at each horizontal branch connection.

4 Hangers shall not be placed on the coupling.

5 Vertical water lines shall be permitted to be supported in accordance with recognized engineering principles with regard to expansions and contraction, where first approved by the Authority Having Jurisdiction.

6 For expansion joints, see Table 313.3.1.

Minn. R. agency 222, ch. 4714, pt. 4714.0313

40 SR 71; 45 SR 1007