Ga. Comp. R. & Regs. 110-11-1-.09

Current through Rules and Regulations filed through October 17, 2024
Rule 110-11-1-.09 - Adoption of Amendments to Codes Effective January 1, 2000

The following amendments to codes are hereby adopted by the Board of Community Affairs as amendments to the Georgia State Minimum Standard Codes for Construction:

GEORGIA AMENDMENTS TO THE 1994 STANDARD BUILDING CODE

Chapter 10 Means of Egress

Section 1005 Special Exit Requirement

* Revise subsection 1005.6 Mezzanines, to read as follows:

The State's minimum requirements for means of egress from mezzanines shall be established by the Life Safety Code. Areas not specifically addressed by the Life Safety Code and which are addressed by the Standard Building Code, the Standard Building Code shall be used as a supplement.

Chapter 16 Structural Loads

Section 1609 Load Combinations

* Revise Section 1609.2 regarding strength design to read as follows:

Except for load combinations which include seismic, load factors for ultimate strength of concrete, LRFD of wood and plastic design or LRFD of steel shall be indicated in the appropriate design standards referenced in this code. (Remainder of section unchanged)

Chapter 19 Concrete

Section 1906 Mixing and Placing Concrete

* Add a new Section 1906.1.2 to read as follows:

1906.1.2 Cells and cavities in masonry units of foundation and basement walls shall be cleaned of all trash, debris, wood scraps, and other extraneous content before concrete placement.

Chapter 23 Wood

Section 2301 Scope

* Add the following standard to subsection 2301.2.5:

American Forest and Paper Association

AF&PA/ASCE 16-95 Load and Resistance Factor Design (LRFD)

Standard for Engineered Wood Construction.

*Revise subsection 2301.4.7 to read as follows:

Hardwood and decorative plywood shall be manufactured and identified as required in ANSI/HPVA HP-1.

Section 2304 Protection Against Decay and Termites

*Add a new Section 2304.6 to read as follows:

2304.6 All Concrete or mortar excess along the exterior foundation perimeter shall be broken away and removed prior to chemical soil treatment of the exterior in order to enhance penetration of the chemical into the soil which is directly adjacent to the exterior.

Chapter 26 Plastic

Section 2603 Foam Plastic Insulation

* Add an exception to subsection 2603.1.3 to read as follows:

1. Where an approved method of protecting the foam plastic and structure from subterranean termite damage is provided.

(renumber the remaining exceptions)

Chapter 35 Reference Standards

Section 3502 Referenced Standards

* Add the following standard:

Standard Designation Section

AF&PA/ASCE Load and Resistance Factor Design (LRFD) Standard for Engineered Wood Construction. 16-95 2301.2.5

* Delete reference standard ANSI/HPMA HP-83, NfoPA Design Values for Joists and Rafters and NfoPA National Design Specification for Wood Construction 1991 and Design Values for Wood Construction, July 1991, NfoPA Span Table for Joist and Rafters, 1993, NfoPA Technical Report No. 7. The Permanent Wood Foundation System, 1/87, NfoPA Wood Construction Data No. 5 Heavy Timber Construction Details, 1990 and substitute the following standards respectively:

Standard Designation Section

ANSI/HPVA HP-1-1994 Hardwood and decorative Plywood 2301.4.7
AF & PA Design Values for Joists and Rafters, 1997 2301.5

ANSI/AF&PA National Design Specification for Wood Construction

709.6.3.3

(NDS®), 1997 and Design Values for Wood Construction, 1997, 1707.3.1 a Supplement to the National Design Specification

2301.2.5
2310.3.2
2310.4.3
2311.3.2
2311.4.2
2312.4
2312.4.5.1
312.4.5.2
2312.4.6
AF&PA Span Table for Joist and Rafters, 1993 2307.3.1
2309.1.1
AF&PA Technical Report No. 7, The Permanent Wood Foundation System, 1/87 1804.8
2306.3
AF & PA Wood Construction Data No. 5,Heavy Timber Construction Details, 1990 2301.2.5

Section 3505 Organizations

* Change the names and addresses of the HPMA and the NfoPA respectively, to read as follows:

HPVA

Hardwood Plywood & Veneer

Association

P. O. Box 2789

Reston, Virginia 22090-2789

AF&PA

American Forest and Paper

Association

111 19th Street, NW, Suite 800

Washington, DC 20036

(The remainder of the section is unchanged)

GEORGIA AMENDMENTS TO THE CABO ONE AND TWO FAMILY DWELLING CODE,1995 EDITION

Chapter 3 Building Planning

Section 323 Protection Against Termites

Subsection 323.1.1 Foam Plastics

* Add an exception number 2 (and number the existing exception "1") to subsection 323.1.1 Foam Plastics to read as follows:

2. Where an approved method of protecting the foam plastic and structure from subterranean termite damage is provided.

* Add a new Section 323.4 to read as follows:

323.4 Cells and cavities in masonry units of foundation and basement walls shall be cleaned of all trash, debris, wood scraps, and other extraneous content before concrete placement.

* Add a new Section 323.5 to read as follows:

323.5 All Concrete or mortar excess along the exterior foundation perimeter shall be broken away and removed prior to chemical soil treatment of the exterior in order to enhance penetration of the chemical into the soil which is directly adjacent to the exterior.

* Add a new Section 325 to read as follows:

325 Deck Construction

325.1 Application: The provisions of this section shall control the design and construction of exterior balconies, decks, and porches.

325.1.2 Requirements: Exterior decks, porches, and its structural elements shall be capable of accommodating all superimposed live, dead, and other loads according to Section 301 and all lateral loads in accordance with this code. Fills which support footings, shall be designed, installed and tested in accordance with accepted engineering practice.

325.2 Attachment to structure: Exterior decks, and porches shall be secured to a 11/2 inch main structural member by 1/2 inch bolts installed 32 inches on center or shall be self-supporting and attached as prescribed in 325.2.

325.2.1 Flashing: Exterior balconies, decks, and porches shall be flashed in accordance with Section 703.8.

325.3 Framing Details: Framing members shall be fastened in accordance with Table 602.3a using corrosion resistant fasteners or equivalent. Floor joists shall be supported by a minimum of 11/2 inch bearing surface.

325.4 Bracing: Adequate bracing shall be provided to resist lateral movement.

325.5 Footings: Footings shall comply with Section 403.

325.6 Guardrails: Guardrails shall comply with Section 315.3, and 315.4.

325.7 Stairs: Stairs leading from exterior balconies, decks, and porches shall comply with Section 314.

Chapter 4 Foundations

Section 403 Footings

Subsection 403.1 General

* Revise Subsection 403.1 so as to read as follows:

403.1 General All exterior walls shall be supported on continuous solid masonry or concrete footings, wood foundations, or other approved structural systems which shall be of sufficient design to support safely, the loads imposed as determined from the character of the soil and, except when erected on solid rock or otherwise protected from frost, shall extend below the frost line as specified in Table 301.2a. Minimum sizes for concrete or masonry footings and anchor bolt placement shall be set forth in Table 403.1 and Figure 403.1a. Footing for wood foundations shall be in accordance with the details set forth in Section 404.2, Figure 403.1b and 403.1c.

GEORGIA AMENDMENTS TO THE STANDARD FIRE PREVENTION CODE, 1994 EDITION

Chapter 6 Fire Protection

Section 603 Installation and maintenance of Fire Protection Systems and Appliances

Subsection 603.3 Portable Fire Extinguishers

* Delete subsection 603.3 in its entirety and substitute the following:

603.3 Portable Fire Extinguishers The State's minimum requirements for portable fire extinguishers shall be established by the Life Safety Code. Areas not specifically addressed by the Life Safety Code but which are addressed by the Standard Fire Prevention Code or the Standard Building Code, the Standard Fire Prevention Code or the Standard Building Code shall be used as a supplement.

Chapter 9, Flammable and Combustible Liquids

Section 907 Service Stations

Subsection 907.3 Storage and Handling

* Delete subsection 907.3.5.6 in its entirety and substitute the following:

See NFiPA 30A, Section 2-4.2 Storage Tanks for requirements regarding storage tanks.

GEORGIA AMENDMENTS TO THE STANDARD PLUMBING CODE, 1994 EDITION

Chapter 5 Water Heaters

Section 506 Connections

* Add a sentence to the end of subsection 506.2 to read as follows:

Hot water supply systems in buildings, where the developed length of hot water piping from the source to the farthest fixture exceeds 100 feet, shall maintain heated water temperature in all supply piping to within 40 feet of any heated water outlet.

Chapter 6 Water Supply and Distribution

Section 607 Sizing of Water Distribution Systems

Subsection 607.9 Water Pressure Reducing Valve of Regulators

* Delete subsection 607.9.3 in its entirety.

* Delete subsection 607.9.4 in its entirety.

Chapter 7 Sanitary Drainage

Section 704 Building Sewer

Subsection 704.6 Minimum Size Building Sewer

* Revise Subsection 704.6 to read as follows:

No Building sewer can be less than 4 inches in size with the exception of a branch, not less than 2 inches in size, serving a detached garage, accessory building or forced lines.

Subsection 704.7 Back Water Valves

* Add a new subsection 704.7 Back Water Valves to read as follows:

704.7 Back Water Valves

704.7.1 Fixture Branches

Backwater valves shall be installed in the branch of the building drain, which receives only the discharge from fixtures located within the such branch on the same floor, and shall be located below grade. Where fixtures are located below the level of the top of the first upstream manhole, such fixtures shall be protected by a backwater valve.

704.7.2 Material

Backwater valves shall have all bearing parts of corrosion resistant material. Backwater valves shall comply with ASME A112.14.1, CSA CAN/CSA-B181.1, or CSA CAN/CSA-B181.2

704.7.3 Seal

Backwater valves shall be so constructed as to insure a mechanical seal against backflow.

704.7.4 Diameter

Backwater valves, when fully open, shall have a capacity not less than that of the pipes in which they are installed.

704.7.5 Location

Backwater valves shall be so installed to be accessible for service and repair.

Chapter 9 Vents

Section 902 Definitions

* Revise the definition of branch vent as follows:

BRANCH VENT - a vent connecting one or more individual vents with a vent stack, or stack vent or terminating in the open air.

Section 920 Size and Length of Vents

* Add a new section 920.4.1 to read as follows:

920.4.1 A branch vent shall only vent fixtures on the same floor level that connect to a horizontal branch or fixture branch.

Chapter 11 Storm Drainage

Section 1112 Backwater Valves

* Delete Section 1112 Backwater Valves in its entirety. Refer to Section 704.7 for requirements regarding backwater valves.

THE 1999 EDITION OF THE NATIONAL ELECTRICAL CODE WITH GEORGIA AMENDMENTS

* The 1999 Edition of the National Electrical Code is hereby adopted in its entirety as if quoted verbatim herein.

The following Georgia Amendments to the 1999 Edition of the National Electrical Code are adopted in conjunction thereto:

Chapter 2 Wiring and Protection

Article 210 Branch Circuits

Section 210-8(b)Other Dwelling Units

* Add a new location to the list of locations as follows:

3) Within 6 feet of a sink or basin, excluding those listed in Section 517-21.

Section 210-70 Lighting Outlets Required

* Amend subsection 210-70(a)(1) Habitable Rooms to read as follows:

(1) Habitable Rooms. At least one wall switch-controlled lighting outlet "to provide illumination" shall be installed in every habitable room and bedroom. "A lighting fixture shall be permitted to be installed meeting the requirements of Section 410-8(b), (c) and (d)."

* Add and exception to subsection 210-70(a)(3) Storage or Equipment Space to read as follows: Exception: No lighting is required in attic spaces that have no equipment and the space is less than 30" in continuous height for a distance of 72" in depth when measured perpendicular to the access opening. If a light fixture is installed in such spaces it shall meet the requirement of Section 410-8(a).

Article 220 Branch-Circuit, Feeder and Service Calculations

Section 220-30 Optional Calculation-Dwelling Unit

* Amend subsection 220-30(c)so as to read as follows:

(c) Heating and air-conditioning Load. Include the largest of the following five selections (load in kVA). 100 percent of the nameplate rating(s) of the air conditioning and cooling, including heat pump compressors.

100 percent of the nameplate ratings of electric thermal storage and other heating systems where the usual load is expected to be continuous at the full nameplate value. Systems qualifying under this selection shall not be calculated under any other selection in (c). 65 percent of the nameplate ratings(s) of the central electric space heating, including integral supplemental heating in heat pumps. 65 percent of the nameplate rating(s) of electric space heating if less than four separately controlled units. 40 percent of the nameplate ratings(s) of electric space heating if four or more separately controlled units.

Article 250 Grounding

Section 250-104 Bonding of Piping Systems and Exposed Structural Steel Subsection 250-104(b)Metal Gas Piping

* Add the following to subsection 250-104(b):

The bonding jumper shall be sized in accordance with Table 250-122 using the rating of the circuit that may energize the piping. The equipment grounding conductor for the circuit that may energize the piping shall be permitted to serve as the bonding means.

Chapter 3 Wiring Methods and Materials

Article 333 Armored Cable

Section 333-3 Uses Permitted

* Add the following to Section 333-3:

Armored cable without the bonding strip inside the armor of the cable shall be limited for use only in existing installations and limited to six feet in any ground return path or be protected by GFCI or by AFCI when the cable exceeds six feet in length.

FPN: Armored cable without the bonding strip has a high impedance ground return path in lengths exceeding six feet and constitutes a fire or shock hazard due to ground faults.

Article 364 Busways

Section 364-9 Overcurrent Protection

* Revise Section 364-9 to read as follows:

(a) General. Overcurrent protection shall be provided in accordance with Sections 364-10 through 364-13.

(b) Residential Occupancies. Residential occupancies shall be ground-fault protected when provided for solidly grounded wye busways of more than 100 volt to ground, but not exceeding 600 volts phase-to-phase for each overcurrent device rated 1000 amperes or more.

Exception to (b): For existing buildings where records indicate the systems have been adequately maintained."

Chapter 4 Equipment for General Use

Article 410 Lighting Fixtures, Lampholders, Lamps and Receptacles

Section 410-57(b)Wet Locations

* Delete Section 410-57(b) and substitute the following:

410-57 (b). Wet Locations a receptacle installed in a wet location shall be in a weatherproof enclosure, the integrity of which is not affected when the attachment plug cap is inserted or removed.

Chapter 6 Special Equipment

Article 695 Fire Pumps

Section 695-6 Power Wiring

Subsection 695-6(b)Circuit Conductors

* Amend subsection 695-6(b)so as to read as follows: They shall be permitted to be routed through a building(s) encased in 2 in. (50.8mm) of concrete, or they shall be permitted to be a listed electrical circuit protective systems with a minimum of 1-hour fire resistance with a minimum of 1-hour fire resistance.

Chapter 7 Special Conditions

Article 700 Emergency Systems

Section 700-9 Wiring, Emergency System

Subsection 700-9(d)(1) Fire Protection

* Amend subsection 700-9(d)(1) as follows: Delete letter (d) under subsection 700-9(d)(1) and reletter the remaining conditions.

Appendix D

* Correct Example No. D2 in Appendix D so as to read as follows:

Example No. D2(c). (Page 70-610) Optional Calculation for One- Family Dwelling with Heat Pump (Single-Phase, 240/120-Volt Service). (see Section 220-30).

Heat Pump and Supplementary Heat*:

20.76 kVA × 65% = 13.49 kVA

Totals
Net general load 19,280 VA
Heat pump and supplementary heat 13,490 VA
Total 32770 VA

32.77 kVA × 1000 ÷ 240 V = A 136.5 A

This dwelling unit would be permitted to be served by a 150-A service.

Ga. Comp. R. & Regs. R. 110-11-1-.09

O.C.G.A. Sec. 8-2-20et seq.

Original Rule entitled "Adoption of Amendments to Codes Effective January 1, 2000" adopted. F. Sept. 23, 1999; eff. Jan. 1, 2000, as specified by the Agency.