49 C.F.R. § 192.743

Current through October 31, 2024
Section 192.743 - Pressure limiting and regulating stations: Capacity of relief devices
(a) Pressure relief devices at pressure limiting stations and pressure regulating stations must have sufficient capacity to protect the facilities to which they are connected. Except as provided in § 192.739(b) , the capacity must be consistent with the pressure limits of § 192.201(a) . This capacity must be determined at intervals not exceeding 15 months, but at least once each calendar year, by testing the devices in place or by review and calculations.
(b) If review and calculations are used to determine if a device has sufficient capacity, the calculated capacity must be compared with the rated or experimentally determined relieving capacity of the device for the conditions under which it operates. After the initial calculations, subsequent calculations need not be made if the annual review documents that parameters have not changed to cause the rated or experimentally determined relieving capacity to be insufficient.
(c) If a relief device is of insufficient capacity, a new or additional device must be installed to provide the capacity required by paragraph (a) of this section.

49 C.F.R. §192.743

Amdt. 192-93, 68 FR 53901 , Sept. 15, 2003, as amended by Amdt. 192-96, 69 FR 27863 , May 17, 2004