Current through September 30, 2024
Section 120.372 - Equipment and conductor grounding(a) All metallic enclosures and frames of electrical equipment must be permanently grounded to the hull on a metallic vessel. On a nonmetallic vessel, the enclosures and frames of electrical equipment must be bonded together to a common ground by a normally non-current carrying conductor. Metallic cases of instruments and secondary windings of instrument transformers must be grounded.(b) On a nonmetallic vessel, where a ground plate is provided for radio equipment, it must be connected to the common ground.(c) Equipment grounding conductors must be sized in accordance with Section 250-95 of the NEC (NFPA 70), or other standard specified by the Commandant.(d) Each insulated grounding conductor of a cable must be identified by one of the following means. (1) A green braid or green insulation;(2) Stripping the insulation from the entire exposed length of the grounding conductor; or(3) Marking the exposed insulation of the grounding conductor with green tape or green adhesive labels.(e) Cable armor must not be used to ground electrical equipment of systems.