46 C.F.R. § 120.322

Current through September 30, 2024
Section 120.322 - Multiple generators

When a vessel is equipped with two or more generators to supply ship's service power, the following requirements must be met:

(a) Each generator must have an independent prime mover; and
(b) The generator circuit breakers must be interlocked to prevent the generators from being simultaneously connected to the switchboard, except for the circuit breakers of a generator operated in parallel with another generator when the installation meets §§ 111.12-11(f) , and 111.30-25(d) in subchapter J of this chapter.

46 C.F.R. §120.322