Cal. Code Regs. tit. 23 § 2643.1

Current through Register 2024 Notice Reg. No. 45, November 8, 2024
Section 2643.1 - Tank Integrity Testing Requirements

Tank integrity testing shall meet the requirements of section 2643(f) and shall be conducted using one of the two methods in subsections (a) or (b) below. Tank integrity test methods shall account for the effects of thermal expansion or contraction of the product, vapor pockets, tank deformation, evaporation or condensation, and the presence of water in the backfill:

(a) A volumetric tank integrity test shall be capable of detecting a release of 0.1 gallon per hour from any portion of the tank when the tank is at least 65% full of product or at any product level if the product-filled portion of the tank is tested under pressure equivalent to that of a full tank. If any volumetric tank integrity test is conducted at a product level lower than the overfill protection device set point, a test meeting the requirements of subsection (b) must be used to test the ullage portion of the tank.
(b) A nonvolumetric tank integrity test shall be capable of detecting a release of 0.1 gallon per hour from any portion of the tank at any product level.

Cal. Code Regs. Tit. 23, § 2643.1

1. New section filed 4-5-94; operative 5-5-94 (Register 94, No. 14).
2. Editorial correction of HISTORY 1 (Register 2000, No. 31).

Note: Authority cited: Sections 25299.3 and 25299.7, Health and Safety Code. Reference: Section 25292, Health and Safety Code; and 40 CFR 280.40 - 280.45.

1. New section filed 4-5-94; operative 5-5-94 (Register 94, No. 14).
2. Editorial correction of History 1 (Register 2000, No. 13).