A newly-installed distribution reservoir or distribution reservoir that has been taken out of service for repair or inspection shall be disinfected and sampled for bacteriological quality in accordance with the American Water Works Association Standard C652-02, which is hereby incorporated by reference. If the results of the bacteriological sampling are positive for coliform bacteria, the reservoir shall be resampled for bacteriological quality and the test results shall be submitted to the State Board for review and approval before the reservoir is placed into service.
Cal. Code Regs. Tit. 22, § 64582
2. Change without regulatory effect amending section and NOTE filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).
Note: Authority cited: Sections 116271, 116350 and 116375, Health and Safety Code. Reference: Sections 116275, 116375 and 116535, Health and Safety Code.
2. Change without regulatory effect amending section and Note filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).