Current through Register 2024 Notice Reg. No. 45, November 8, 2024
Section 565.2 - Selection by Hazard(a) Extinguishers shall be selected for the specific class or classes of hazards to be protected in accordance with the following subdivisions.(b) Extinguishers for protecting Class A hazards shall be selected from the following: Water-type, halogenated agent types, multipurpose dry chemical and wet chemical type.(c) Extinguishers for protection of Class B hazards shall be selected from the following: carbon dioxide, dry chemical types, halogenated agent types, and water-type and water chemical extinguishers rated for Class B hazards.(d) Extinguishers for protection of Class C hazards shall be selected from the following: carbon dioxide, dry chemical types, halogenated agent types, and water mist types rated for Class C. Carbon dioxide extinguishers equipped with metal horns are not considered safe for use on fires in energized electrical equipment and, therefore, are not classified for use on Class C hazards.(e) Extinguishers and extinguishing agents for the protection of Class D hazards shall be of types approved for use on the specific combustible-metal hazard.Cal. Code Regs. Tit. 19, § 565.2
1. Renumbering and amendment of former section 565.1 to new section 565.2 filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
2. Repealer of subsection (f) filed 2-28-2007; operative 3-30-2007 (Register 2007, No. 9). Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.
1. Renumbering and amendment of former section 565.1 to new section 565.2 filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
2. Repealer of subsection (f) filed 2-28-2007; operative 3-30-2007 (Register 2007, No. 9).